Hood length times a duty-specific rate gives net exhaust CFM.
This hood cfm calculator multiplies the hood's front-face length in feet by the applicable CFM per linear foot. For wall-mounted canopies, light, medium, heavy, and extra-heavy duty use 200, 300, 400, and 550 CFM per foot. Single-island canopies use 400, 500, 600, and 700 CFM per foot. These are the unlisted-canopy rates in IMC 2021 sections 507.5.1 through 507.5.4; adopted editions and local amendments may differ. Use the highest appliance duty for the whole hood, rather than averaging the appliances. Net exhaust excludes air supplied directly into the hood cavity. This commercial kitchen hood calculator does not size a fan motor, grease duct, makeup air unit, or fire-suppression system. A mechanical designer must coordinate the whole system and the local authority's requirements.